Fluke 1623 Kit Basic GEO Earth Ground Tester Kit
Be the first to review this product
Quick Overview
Advanced technology for all your earth ground testing applications
The new Fluke 1620 Series Earth Ground Testers not only measure ground resistance using the classic ‘fall of potential test’ but also enable time saving testing using the ‘selective’ and ‘stakeless’ methods. ‘Selective’ testing does not require the electrode under test to be disconnected during the measurement, thus increasing safety. The simple ‘stakeless’ method quickly checks ground connections using two current transformers (probes) clamped around the ground conductor under test. Offering ‘one-button’ simplicity, the 1623 is an all-in-one earth ground tester, while the 1625 has extra versatility for more demanding applications.
Earth ground resistance and soil resistivity should be measured when:
- Designing earth ground systems
- Installing new ground system and electrical equipment
- Periodically testing ground and lightning protection systems
- Installing large electrical equipment such as transformers, switchgears, machines, etc.
Features
- One-button measurement concept
- 3- and 4-pole earth ground measurement
- 4-Pole soil resistivity testing
- 2-Pole resistance measurement AC
- Selective testing, no disconnection of ground conductor (1 clamp)
- Stakeless testing, quick ground loop testing (2 clamps)
- Measuring frequency 128 Hz
- Safety rating - CAT II 300 V
Includes
- Protective holster with carry belt
- 2 test leads
- 2 alligator clips
- 1 shorting jumper
- Users manual
- Stake/reel set
- 4 pole
- selective/stakeless clamp set
What is ground, and what does it doΩ;
The NEC, National Electrical Code, defines a ground as a “conducting connection, whether intentional or accidental between an electrical circuit or equipment and the earth, or to some conducting body that serves in place of the earth.” When talking about grounding it is actually two different subjects, earth grounding and equipment grounding. Earth grounding is an intentional connection from a circuit conductor usually the neutral to a ground electrode placed in the earth. Equipment grounding is to ensure that operating equipment within a structure is properly grounded.
These two grounding systems are required to be separate except for a connection between the two systems to prevent differences in potential from a possible flashover from a lightning strike. The purpose of a ground besides the protection of people, plants and equipment is to provide a safe path for the dissipation of Fault Currents, Lightning Strikes, Static Discharges, EMI and RFI signals and interference.
Checking ground electrode impedance for commercial, industrial and residential buildings
This application note explains earth ground principles and safety in more depth and then describes the principle testing methods:
- Three- and four-pole Fallof- Potential testing
- Selective testing
- stakeless testing
- 2 pole testing
Want to read moreΩ; Download this and other application notes at www.fluke.co.uk/applications
Product Tags/Keywords
Add Your Tags/Keywords:
Technical Specification
- Resistance ranges
0 to 20 kΩ - Operating error
± 5% - Test voltage
48V - Short circuit current
> 50mA - Battery type
6 x AA alkaline cells - Size (HxWxD)
110 mm x 180 mm x 240 mm - Weight
1.1 kg (including batteries)
Two Year Warranty
Temperature ranges
| Working temperature | -10 °C to 50 °C (14 °F to 22 °F) |
|---|---|
| Operating temperature | 0 °C to 35 °C (32 °F to 95 °F) |
| Storage temperature | -20 °C to 60 °C (-4 °F to 140 °F) |
| Reference temperature | 23 °C to ± 2 °C (73 °F to ± 4 °F) |
The chart of four temperature ranges for the instrument exist to satisfy European Standards requirements; the instrument can be used over the full working
temperature range by using the temperature coefficient to calculate accuracy at the ambient temperature of use.
| Temperature coefficient | ± 0.1 % of reading/K |
|---|---|
| Intrinsic error | Refers to the reference temperature range and is guaranteed for 1 year |
| Operating error | Refers to the operating temperature range and is guaranteed for 1 year |
| Climatic class | C1 (IEC 654-1), -5 °C to +45 °C (23° to +115° F), 5 % to 95 % RH |
| Protective type | IP56 for case, IP40 for battery door according to EN60529 |
| Safety | Protection by double and/or reinforced insulation. max. 50 V to earth |
| EMC (Emission Immunity) | IEC 61326-1:1997 Class A |
| Quality system | Developed, designed and manufactured according to DIN ISO 9001 |
| External voltage | V ext, max = 24 V (dc, ac < 400 Hz), measurement inhibited for higher values |
| V ext rejection | > 120 dB (162/3, 50, 60, 400 Hz) |
| Measuring time | Typical 6 sec. |
| Max. overload | 250 V rms (pertains to misuse) |
| Auxiliary power | 6 x 1.5 V mignon cells alkali-manganese (type AA LR6) |
| Battery life span | Typical > 3,000 measurements |
| Dimensions (WxHxD) | 250 mm x 133 mm x 187 mm (9.75 in x 5.25 in x 7.35 in) |
| Weight | 1.1 kg (2.43 lb) including batteries |
RA 3-pole ground resistance measurement (IEC 1557-5)
| Switch position | Resolution | Measuring range | Intrinsic error | Operating error |
|---|---|---|---|---|
| RA 3-pole | 0.001 Ω to 10 Ω | 0.001 Ω to 19.99 kΩ | ± (2 % rdg + 3 d) | ± (5 % rdg + 3 d) |
For 2-pole measurements connect terminals H and S with the supplied connector cable.
Measuring principle: Current and voltage measurement
| Measuring voltage | Vm = 48 V ac |
|---|---|
| Short-circuit current | > 50 mA |
| Measuring frequency | 128 Hz (125 Hz on request) |
| Probe resistance (RS+ RES) | Max. 100 kΩ; |
| Auxiliary earth electrode resistance (RH) | Max. 100 kΩ; |
| Additional error from RH and RS | RH[kΩ;]• • •RS[kΩ;/RA[Ω;]• • •0.2 % |
| Monitoring of RS, and RH with error indicator | |
| Automatic range selection | |
RA 4-pole ground resistance measurement (IEC 1557-5)
| Switch position | Resolution | Measuring range | Intrinsic error | Operating error |
|---|---|---|---|---|
| RA 4-pole | 0.001 Ω to 10 Ω | 0.001 Ω to 19.99 kΩ | ± (2 % rdg + 3 d) | ± (5 % rdg + 3 d) |
Measuring principle: Current/voltage measurement
| Measuring voltage | Vm = 48 V ac |
|---|---|
| Short-circuit current | > 50 mA |
| Measuring frequency | 128 Hz (125 Hz on request) |
| Probe resistance (RS+ RES) | Max. 100 kΩ; |
| Auxiliary earth electrode resistance (RH) | Max. 100 kΩ; |
| Additional error from RH and RS | RH[kΩ;]• • •RS[kΩ;/RA[Ω;]• • •0.2 % |
| Monitoring of RS, and RH with error indicator | |
| Automatic range selection | |
RA 3-pole selective ground resistance measurement with current clamp (RA )
| Switch position | Resolution | Measuring range | Intrinsic error | Operating error |
|---|---|---|---|---|
| RA 3-pole | 0.001 O to 10 O | 0.001 O to 19.99 kΩ | ± (7 % rdg + 3 d) | ± (10 % rdg + 5 d) |
Measuring principle: Current/voltage measurement (with external current clamp)
| Measuring voltage | Vm = 48 V ac |
|---|---|
| Short-circuit current | > 50 mA |
| Measuring frequency | 128 Hz (125 Hz on request) |
| Probe resistance (RS) | Max. 100 kΩ; |
| Auxiliary earth electrode resistance (RH) | Max. 100 kΩ; |
| Monitoring of RS, and RH with error indicator | |
| Automatic range selection | |
| Measurement is not performed if the current through the current clamp is too low | |
RA 4-pole selective ground resistance measurement with current clamp (RA )
Measuring principle: Current/voltage measurement (with external current clamp)
| Measuring voltage | Vm = 48 V ac |
|---|---|
| Short-circuit current | > 50 mA |
| Measuring frequency | 128 Hz (125 Hz on request) |
| Probe resistance (RS) | Max. 100 kΩ; |
| Auxiliary earth electrode resistance (RH) | Max. 100 kΩ; |
| Monitoring of RS, and RH with error indicator | |
| Automatic range selection | |
| Measurement is not performed if the current through the current clamp is too low | |
Stakeless ground loop measurement
Measuring principle: Stakeless measurement of resistance in closed loops using two current transformers
| Measuring voltage | Vm = 48 V ac (primary) |
|---|---|
| Measuring frequency | 128 Hz (125 Hz on request) |
| Noise current (IEXT) | Max. IEXT = 10 A (ac) (RA < 20 Ω;) |
| Max. IEXT = 2 A (ac) (RA > 20 Ω;) |
Auomatic range selection
The information regarding stakeless ground loop measurements is only valid when used in conjunction with the recommended current clamps at the minimum distance specified.