You have no items in your shopping basket.
Amprobe Telaris 0100 Plus Installation Tester
Be the first to review this product
Quick Overview
We supply installation testers, click to see the latest Amprobe installation testers.
Key Features
- Loop resistance measurement up to 265 V
- Line resistance measurement up to 440 V
- Prospective short circuit current measurement
- RCD measurements (contact voltage, trip time, trip current - ramp method)
- Low Ohm measurement
- Insulation measurement with 100, 250, 500 V
- Voltage and frequency measurement
- Rotary field test
- Integrated memory for approx. 500 measurement values
- Standard, built-in IR RS-232 interface for transferring measurement data to the PC
- Software es control for recording test results is available as option
- Integrated socket test with contact electrode to enable the user to quickly establish incorrectly installed sockets and/or protective conductor failures
- Clear and large LCD providing the user with an optimum visual indication of both test values and limits
- Auto power off
- Measurement of loop resistance and prospective short circuit current measurement without tripping the RC
Product Tags/Keywords
Add Your Tags/Keywords:
Use spaces to separate tags. Use single quotes (') for phrases.
Technical Specification
| FEATURES | ||
|---|---|---|
| Display | LCD, 3-digit, 1999 Digits Measurement Ranges | Resolution |
| Voltage | 1 - 440 V | 1V AC/DC |
| Frequency | 10 - 99,9 Hz | 0,1 Hz |
| Loop Impedance | 0,1519,99./199,9/1999 Ω; | 0,01/0,1/1 Ω; |
| Prospective Short | ||
| Circuit Current | 0,10 A - 1,7 kA | 0,01A - 0,1 kA |
| Input Voltage Range | 195 - 264 V 50/60 Hz | |
| Test Current | approx. 4,6 A (at 230 V) | |
| Line Resistance | 0,1519,99Ω;/199,9/1999 Ω; | 0,01/0,1/1 Ω; |
| Prospective Short | ||
| Circuit Current | 0,10 A - 2,7 kA | 0,01A - 0,1 kA |
| Input Voltage Range | 195 - 440 V 50/60 Hz | |
| Test Current | approx. 4,6 A (at 230 V) | |
| Loop Resistance (without tripping the RCD) | 0,5 - 19,99Ω;/199,9/1999 Ω; | 0,01/0,1/1Ω; |
| Prospective Short | ||
| Circuit Current | 0,50 A - 0,5 kA | 0,01A - 0,1kA |
| Input Voltage Range | 195 - 264 V 50/60 Hz | |
| Test Current | approx. 5 mA (at 230 V) | |
| Insulation Resistance | 0,05 - 19,99/199,9 MΩ; | 0,01/0,1 MΩ; |
| Test Voltage | 100, 250, 500 V DC | |
| Low Ohm Measurement | 0,05 - 19,99/199,9/1999 Ω; | 0,01/0,1/1 Ω; |
| Test Current | > 200 mA DC | |
| RCD-Test Nominal | 10, 30, 100, 300, 500mA | |
| currents | 0,5 x 30mA, 5 x 30mA | |
| selective: | 100, 300, 500mA | |
| Measurement | Contact voltage, | |
| Functions | trip time, Tripping current test with ramp method | |
| Contact Voltage | 1 - 63 V | |
| Earth Resistance | 101999 Ω;/19,99 kΩ; | 1 Ω;/0,01 kΩ; |
| Tripping Time | 1 - 500 ms | 1 ms |
| Tripping Current | 40 - 140% of IΩ;N (in 10% steps) | |
| Rotary Field Test | ||
| Input Voltage Range | 100 - 440 V 50/60 Hz | |
| Data memory | approx. 500 values | |
| Interface | IR-RS-232 | |
| Safety complying with | IEC61010, EN61010, DIN VDE 0411/ | |
| IEC61557, EN61557, DIN VDE 0413 | ||
| Measurement category | CAT III/440V | |
| Pollution Degree | 2 | |
| Protection Degree | IP 40 | |
| Power Supply | 6 x 1,5 V, IEC LR6 | |