Metrel Instaltest 61557
Email to a FriendView Product Description
Add to Wishlist
Measuring functions
Complete range of test functions in accordance with IEC / EN 61557:
Other features
Internal memory with a capability to store up 1000 test results that can later be transferred to a personal computer.
Software
Software package InstalLink compatible with MS Windows operation systems allows download of test results from the instrument to a personal computer. Handy tool for creating test reports.
Technical data
Dimensions (w x h x l): 265 x 110 x 185 mm
Mass (without accessories): 1,8 kg
Standard Set
Technical Specification
Dimensions (w x h x l): 345 x 160 x 335 mm
Mass (without accessories): 9 kg
► Insulation Resistance
Display range 0 – 1000MOhms (Un=250 V) 0 – 200 MOhms (Un<250 V)
Resolution 0.001 0.01 0.1 1 MOhms
Accuracy ±(2 % + 2 Digits)…(0 – 200 MOhms)
Test voltage 50 100 250 500 1000 V
Generator current capability >1 mA
► Continuity of Protection Conductors (single measurement)
Display range 0.00 – 19.99 20.0 – 199.9 200 - 2000 Ohms
Accuracy ±(2 % + 2 Digits)….(0 – 20 O)
Open-terminal test voltage 4 – 7 Vd.c.
Test current >200 mA
Compensation of test leads yes
Automatic polarity exchange yes
► Continuity (continuous measurement)
Display range 0.0 – 199.9 Ohms 200 – 2000 Ohms
Accuracy ±(3 % + 3 Digits)
Short-circuit test current <7 mA
Open-terminal voltage 4 – 7 Vd.c.
► RCD Protection Devices – general data
Nom. test current 10; 30; 100; 300; 500; 1000 mA (0 or 180 °C)
RCD type AC, standard or selective
► RCD – Contact Voltage
Display range 0.00 – 9.99 10.0 – 100 V
Resolution 0.01 0.1 V
Basic accuracy (-0 / +10)% ± 0.2 V (-0 / +10) %
Test current <0.5 I?N
► RCD – Earth/Loop Resistance
Measurement principle with or without probe
Display range 0 – 10 kO
► RCD – Trip out Time
Display range (general type) 0 – 300 ms (0.5 I?N, I?N)
0 – 150 ms (2 I?N) 0 – 40 ms (5 I?N)
Display range (selective type) 0 – 500 ms (0.5 I?N, I?N)
0 – 200ms (2 I?N) 0 – 150 ms (5 I?N)
Accuracy ±3 ms
► RCD – Tripping Current
Display range I? (0.2 – 1.1) I?N
Display range t?/I? 0 – 300 ms
Display range Uci (Uc/I?) 0 – 100 V
► Fault Loop Impedance / Resistance and Ipsc
Display range Z, R, X 0.00 – 19.99 20.0 – 199.9 200 – 2000 Ohms
Accuracy Z, R, X …Eurotest ±(2 % + 3 Digits)
Accuracy R…Instaltest ±(5 % + 5 Digits)
Display range Ipsc 0.06 A – 24.4 kA
Nominal voltage 100 – 264 V 45 – 65 Hz
► Line Impedance / Resistance and Ipsc
Display range Z, R, X 0.00 – 19.99 20.0 – 199.9 200 – 2000 Ohms
Accuracy Z, R, X …Eurotest ±(2 % + 3 Digits)
Accuracy R…Instaltest ±(5 % + 5 Digits)
Display range Ipsc 0.06 A – 42.4 kA
Nominal voltage 100 – 440 V 45 – 65 Hz
► N-PE Loop / Earth Resistance and Ipsc
Test method internal generator (Earth resistance)
Display range R l-pe 0.00 – 19.99 20.0 – 199.9 200 – 2000 Ω
Accuracy R l-pe ±(2 % + 3 Digits)
Display range Ipsc 0.06 A – 24.4 kA
► Phase rotation
Display of result 1.2.3 or 2.1.3
► Voltage Frequency
Display range 0 – 440V 45.0 – 65.0 Hz
Accuracy ±(2 % + 2 D) ± 0.2 Hz
Nominal frequency range 45 – 65 Hz
► Current (True RMS)
Measurement principle current clamp
Display range 0 – 200 Amps
Resolution 0.1 1 mA 0.01 0.1 1A
Basic accuracy ±(5 %)…(0.1 – 100 Amps)
Nominal frequency 50/60 Hz
► Peak Current
Display range 5 – 280 Amps
Basic accuracy ±(5 %)
► Varistor Overvoltage Protection. Devices – Breakdown Voltage
Measurement principle d.c. voltage ramp (500 V/s)
Display range 50 – 1000 V
Accuracy ±(5 % + 10 V)
► Power (one-phase)
Display range 0 – 88 k W/VA/Var
Resolution 0.1 1 0.01 k 0.1 k W/VA/Var
Accuracy ±(7 % + 1 D)
Nominal voltage, frequency 10 – 440 V, 50/60 Hz
Display range cosϕ 0 – 1
► Energy
Calculation W = Σ P × Δt
Display range 0 – 2000 kWh
Accuracy ±(7 % + 1 Digits)
► GENERAL CHARACTERISTICS:
Power supply 6 V (4 × 1.5 V IEC LR14)
Dimensions (w × h × d) 265 × 110 × 185 mm
Weight: 2,1 kg.